In the evaporator, refrigerant enters at some vapor quality between 0% and 100%, and typically exits as a superheated vapor. The analysis for the evaporator shares many features with the analysis employed for the Condenser and the Cooling Coil, but the evaporator’s analysis is significantly more complicated due to the fact that there are moving boundaries on both the refrigerant and air sides. On the refrigerant-side, the moving boundary is between two-phase refrigerant and superheated refrigerant, and on the air-side, there is a moving boundary between wet and dry parts of the coil.
The evaporator is treated as being cross-counter-flow. What this means practically is that the mass flow of air to and total air side surface area for each of the superheated and two-phase portions (assuming each exists), are given by
(1)
which is analogous to the analysis employed for the condenser. On the refrigerant-side, the surface area for superheated and two-phase sections are given by
(2)
In the two-phase section, the target heat transfer rate is given by
(3)
and the heat transfer rate from the partially-wet/partially-dry analysis in section Two-phase on working fluid side is given the name . To begin with, the first guess is that all the heat exchanger is in the two-phase region. If using the outlet quality of saturated vapor () with all the heat exchanger in the two-phase region, and is greater than , too much of the heat exchanger area was given to the two-phase section, and there must be a superheated section as well. Thus, the length fraction is iteratively altered using a bounded solver ( is bounded between 0 and 1). The remaining area is given to the superheated section, so the superheated section circuit length fraction is given by
(4)
In the superheated section, for a given , the analysis is exactly the same as the Cooling Coil, and given by the section Single-phase on working fluid side. As in the cooling coil, the working fluid is single-phase, and the air-side surface may be fully wet, partially wet, or fully dry, and all the inlet conditions for the superheated section are known. The air inlet state to the superheated portion is assumed to be the same as for the two-phase portion because the superheated portion is typically rather small, and both superheated and two-phase portions should see approximately the same inlet air state. The refrigerant properties are calculated using the same single-phase correlations as for the cooling coil.
from CoolProp.CoolProp import Props
from FinCorrelations import FinInputs
from Evaporator import EvaporatorClass
FinsTubes=FinInputs()
FinsTubes.Tubes.NTubes_per_bank=32
FinsTubes.Tubes.Ncircuits=5
FinsTubes.Tubes.Nbank=3
FinsTubes.Tubes.Ltube=0.452
FinsTubes.Tubes.OD=0.009525
FinsTubes.Tubes.ID=0.0089154
FinsTubes.Tubes.Pl=0.0254
FinsTubes.Tubes.Pt=0.0219964
FinsTubes.Fins.FPI=14.5
FinsTubes.Fins.Pd=0.001
FinsTubes.Fins.xf=0.001
FinsTubes.Fins.t=0.00011
FinsTubes.Fins.k_fin=237
FinsTubes.Air.Vdot_ha=0.5663
FinsTubes.Air.Tdb=299.8
FinsTubes.Air.p=101.325
FinsTubes.Air.RH=0.51
FinsTubes.Air.FanPower=438
kwargs={'Ref': 'R410A',
'mdot_r': 0.0708,
'psat_r': Props('P','T',282,'Q',1.0,'R410A'),
'Fins': FinsTubes,
'hin_r':Props('H','T',282,'Q',0.15,'R410A')*1000, #[J/kg]
'Verbosity':0
}
Evap=EvaporatorClass(**kwargs)
Evap.Update(**kwargs)
Evap.Calculate()
print 'Evaporator heat trasfer rate is',Evap.Q,'W'
print 'Evaporator capacity (less fan power) is',Evap.Capacity,'W'
print 'Evaporator fraction of length in two-phase section',Evap.w_2phase,'W'
print 'Evaporator sensible heat ratio',Evap.SHR
If you open an IPython(x,y) shell in the root of the documentation (folder Documentation/Web relative to the main trunk), and run the commands below, you should get
In [5]: execfile('ACHPComponents/ComponentTests/EvaporatorTest.py')
Evaporator heat trasfer rate is 13222.5359037 W
Evaporator capacity (less fan power) is 12784.5359037 W
Evaporator fraction of length in two-phase section 0.89179879315 W
Evaporator sensible heat ratio 0.709186116025
If not, first stop should be the Frequently Asked Questions
Nomenclature
Variable | Description |
---|---|
Total air side area (fins+tubes) [m2] | |
Air-side area for superheated portion of circuit [m2] | |
Air-side area for two-phase portion of circuit [m2] | |
Refrigerant-side area for superheated portion of circuit [m2] | |
Refrigerant-side area for two-phase portion of circuit [m2] | |
Latent heat of refrigerant [J/kg] | |
Mass flow rate of dry air [kg/s] | |
Mass flow rate of dry air in superheated section [kg/s] | |
Mass flow rate of dry air in two-phase section [kg/s] | |
Mass flow rate of refrigerant [kg/s] | |
Target heat transfer rate [W] | |
Heat transfer rate from the partially wet/partially-dry analysis [W] | |
Refrigerant inlet quality [-] | |
Refrigerant outlet quality [-] |